Use this voltage drop calculator to estimate the volts lost along a copper or aluminum cable. For DC and single-phase, VD = 2 × I × R × L ÷ 1000; for three-phase, use √3 instead of 2 (L is one-way length in feet, R in ohm per 1000 ft). Pick DC, single-phase or three-phase, enter voltage, current (or watts), one-way length and wire size, then check the percent drop against your limit and see the smallest wire that passes. Enter one-way length only—the formula already accounts for the return path on DC and single-phase.

Math runs in your browser. Nothing is uploaded.

Voltage drop (V)
—

Voltage drop (%)
—

Voltage at load (V)
—

Result
—

Resistance used (ohm per 1000 ft)
—

Smallest listed size within the limit
—

Estimate only. Uses DC resistance at 75 °C for stranded uncoated copper and aluminum from NEC Chapter 9, Table 8. It ignores reactance, power factor, temperature correction and conduit effects, and is not a substitute for the NEC, local code or a licensed electrician. VD = 2 × I × R × L ÷ 1000 (DC, single-phase); VD = √3 × I × R × L ÷ 1000 (three-phase); L is one-way length in feet, R in ohm per 1000 ft. Power to current: I = W ÷ V (÷ √3 for three-phase, unity power factor). Common guidance is 3% on a branch circuit and 5% overall.

Roof Pitch Calculator · Square Footage Calculator · Concrete Calculator Bags · Ohms Law Calculator · Wire Size Calculator · Amp Calculator

How it works

What is the voltage drop formula?
For DC and single-phase AC, VD = 2 × I × R × L ÷ 1000, where I is current in amps, R is the conductor resistance in ohms per 1000 ft and L is the one-way length in feet. For three-phase, replace 2 with √3 (about 1.732). Percent drop = VD ÷ source voltage × 100. Example: 120 V, 20 A, 100 ft one-way, 12 AWG copper (1.98): 2 × 20 × 1.98 × 100 ÷ 1000 = 7.92 V, which is 6.6%. Enter one-way length only; the 2 (or √3) already covers the return path.
What is an acceptable voltage drop?
A common guideline, found in NEC informational notes rather than as a hard requirement, is a maximum of 3% on a branch circuit or feeder and 5% for feeder and branch circuit combined. Some equipment, local rules or project specs are stricter, so this calculator lets you change the limit (default 3%). Motors and sensitive electronics often need a tighter limit than the 3% guideline.
How does cable length affect voltage drop?
Drop grows in direct proportion to length when wire size and current stay the same. A 20 A load on 12 AWG copper drops 3.96 V (3.3% of 120 V) over 50 ft one-way and 7.92 V (6.6%) over 100 ft. Halving length halves the drop; doubling current doubles it. To keep drop in check on long runs, use a larger wire.
Is copper or aluminum better for voltage drop?
Copper has lower resistance. At 12 AWG, the table value is 1.98 ohm per 1000 ft for copper and 3.25 for aluminum, so aluminum drops about 64% more at the same size and current. Aluminum generally needs to be about two AWG sizes larger to match copper's resistance. Matching copper AWG one-for-one with aluminum is a common mistake—check both ampacity and voltage drop.
Why is the one-way cable length doubled in the formula?
In a DC or single-phase circuit, current flows out on one conductor and returns on the other, so the current travels twice the one-way distance. That is the 2 in 2 × I × R × L. In a balanced three-phase circuit the line-to-line drop uses √3 instead of 2, which reflects the phase relationship between the conductors. If your measured length is already round-trip, halve it before entering it here or you will double-count.